A gas boiler uses roughly 80 to 200 watts while it is running, with a peak of 200 to 400 watts on start-up. Source: Noodstroom Thuis (in Dutch) That is surprisingly little, and it is exactly why you can often keep it going for a full day or more on a power station or a UPS costing a couple of hundred euros. The gas main stays under pressure during an ordinary power cut. It is only your electricity that disappears.
But there is a catch that most articles on this subject walk straight past, and it is the reason people end up standing next to a brand new generator and a boiler that stubbornly refuses to come out of lockout.
A modern gas boiler is fussy. It wants a pure sine wave, it is often sensitive to which way round live and neutral are connected, and its flame supervision works with an ionisation current that runs to earth. A generator or inverter with a floating neutral gives that current nowhere to go, and your boiler duly goes into flame failure. Without burning a single drop of gas.
Below is the whole story: how much power your boiler really needs, how to work out your runtime, the three technical traps, which solution fits your situation, what it costs, and the thing everybody forgets (spoiler: the thermostat).
Why does your boiler stop in a power cut anyway?
The gas still arrives. The gas distribution network does not run on your electricity, so during a normal outage there is usually still pressure in the pipe.
What does disappear is everything that makes that gas useful:
- The fan that supplies combustion air and pushes the flue gases out. No fan, no ignition, because the boiler will not start until the air pressure switch gives it the nod.
- The ignition and the gas valve (the electrically operated valve on the gas train). Without power that valve stays shut. That is a safety function, not a fault.
- The circulation pump that pushes water round your radiators. No pump, no heat in the house, even if the burner were lit.
- The controls and the thermostat. Your room thermostat needs power too, and sometimes it has its own supply.
- The underfloor heating pump or manifold if you have one, plus any zone valves.
So there you are: you have gas, you have a perfectly good boiler, and you are cold. The only thing missing is a couple of hundred watts.
How much power does your boiler need?
This is the sum that decides everything, so do it properly.
| Item | Power |
|---|---|
| Boiler running | 80 to 200 W |
| Peak on start-up | 200 to 400 W |
| Boiler on standby | typically 2 to 10 W |
| Mains-powered room thermostat | 2 to 10 W |
| Separate underfloor heating pump | 30 to 80 W |
| Zone valve | 3 to 10 W each |
Source: Noodstroom Thuis (in Dutch)
As a sanity check: a modern condensing boiler made after 2015 uses around 150 kWh of electricity over a full year, while an older one from before 2010 averages about 450 kWh. Source: Zonneplan (in Dutch) The difference comes mostly from old boilers having a pump that runs flat out day and night, while modern boilers have an efficient pump that only runs when there is a call for heat.
Measure it yourself, it is five minutes of work. Put an energy monitor (one of those plug-in meters costing 10 to 20 euros) between your boiler and the socket and watch it over a winter’s day. You will see the standby draw, the running draw and the start-up peak straight away. That number beats any average from a table, because your boiler is your boiler.
Working out how much battery you need
The trick is that your boiler does not run continuously. It heats until the thermostat is satisfied and then shuts off. How often that happens depends on your insulation, the outside temperature and the indoor temperature you want.
Worked example (realistic assumptions, not gospel):
- Boiler running: 120 W
- Running time on a cold winter’s day: 40 per cent of the time
- Standby the rest of the time: 5 W
- Thermostat: 5 W continuously
Daily consumption: (120 × 24 × 0.4) + (5 × 24 × 0.6) + (5 × 24) = 1152 + 72 + 120 = roughly 1350 Wh per day.
Now add the conversion losses. Reckon on about 15 per cent loss in the inverter, so divide by 0.85. Source: Noodstroom Thuis (in Dutch)
That puts you at roughly 1.6 kWh of usable battery capacity per 24 hours.
| Battery or power station | Heating only | Heating plus fridge, lights and internet |
|---|---|---|
| 500 Wh | about 8 hours | about 3 hours |
| 1,000 Wh | about 15 hours | about 5 hours |
| 2,000 Wh | a good 24 hours | about 10 hours |
| 5,000 Wh | 3 days | about 24 hours |
These runtimes are indicative figures based on the worked example above. Heat deliberately less (one room at 17 degrees instead of the whole house at 20, say) and you will easily get double out of it.
Four ways to double your runtime without a bigger battery:
- Turn the thermostat down. Going from 20 to 17 degrees cuts the running time considerably, and with a jumper on it is perfectly bearable.
- Shut the doors and heat one room. Closing the radiators in unused rooms halves the heat demand without much effort.
- Turn the pump overrun off or shorten it if your boiler lets you.
- Switch off the hot water preheat. A combi boiler that keeps the domestic hot water warm fires up all night long to do it. That costs you battery hours for nothing.
The three traps that put your boiler into lockout
This is where the real difference lies between a working backup supply and an expensive doorstop. All three come down to the same question: how clean is the power you are feeding in?
Trap 1: no pure sine wave
The socket on your wall delivers a smooth sine wave. Cheap inverters and small UPS units deliver a square wave or an approximated sine wave (the so-called modified sine). For a light bulb that is fine. For the electronics and the fan motor in a gas boiler it is not.
Manufacturers generally specify that a generator must deliver a stabilised voltage and a clean 50 Hz frequency, and in practice that means a genuine sine wave, not a crude square wave.
What to buy: anything that explicitly says pure sine wave. If it does not say so, assume it is not one. This is not the place to save money.
Trap 2: live and neutral swapped
Plenty of gas boilers are polarity sensitive. The control board expects live on one terminal and neutral on the other. Swap them and the boiler can go into lockout immediately, or only after a while.
With a normal socket that is not an issue, because the plug only goes in one sensible way. But as soon as you connect an extension lead, an inverter or a generator yourself, that order can flip. If you get an unexplained fault, try the plug the other way round (on a two-pin plug with no fixed orientation) or have an engineer measure the polarity.
Trap 3: the floating neutral (this is the big one)
This is the trap most people come unstuck on, and physically it is rather elegant.
Your boiler checks whether there is actually a flame using an ionisation probe. That probe sits in the flame. Because a flame conducts electricity, a tiny current flows from the probe through the flame to the burner and from there to earth. If the control board measures that current, there is a flame. If it measures nothing, it shuts the gas valve. A sound safety principle.
The problem: that ionisation current runs via the earth of the installation. A portable generator and many cheap inverters have no connection between neutral and earth. They deliver a “floating” supply. There is no earth reference for the ionisation current to flow to, so the boiler detects no flame and goes into flame failure. On Bosch boilers you will see an ionisation fault, for example, but every make has its own code for it.
On forums you will then read the advice to just bond one pole of the generator to earth yourself. Do not do that. You are making a decision about the earthing of an entire supply, and if you get it wrong your RCD no longer works as intended and you can put touchable parts live.
What you should do instead:
- Choose a power station or UPS that is explicitly suitable for gas boilers or heating equipment. Better models make an internal neutral to earth bond in backup mode, and then the ionisation detection works perfectly normally.
- Or have a registered installer fit a permanent backup supply with a changeover switch. They will sort out the earthing and the neutral bond properly.
- Or, with a generator, choose a model supplied as earthed and have an engineer check that it works with your particular boiler.
And most important of all: test it once on an ordinary day. Pull your boiler’s plug out of the socket, plug it into your backup supply, turn the thermostat up and see whether the boiler really ignites and stays lit. Five minutes of work, and you know whether you will be warm in January or not.
The options compared
| Solution | Cost (indicative) | Runtime | Switches over automatically | Noise | Suits |
|---|---|---|---|---|---|
| UPS (pure sine wave, small) | 150 to 400 euros | 1 to 4 hours | yes, within milliseconds | slight hum | bridging short outages |
| Power station (LiFePO4, 1 to 2 kWh) | 500 to 1,500 euros | 10 to 30 hours | only with a UPS function | virtually silent | most households |
| Inverter with battery, permanently installed | 800 to 2,500 euros | as much as you like | yes, with a changeover switch | quiet | anyone wanting it neat and permanent |
| Home battery with backup function | 4,000 to 9,000 euros | one to several days | yes | quiet | anyone already considering one |
| Generator (petrol, inverter type) | 400 to 1,500 euros | as long as you have fuel | no | loud, must sit outdoors | long outages, whole house |
These are realistic ranges for consumer equipment, excluding installation costs.
Which one do you choose?
Do you live somewhere with the occasional outage of a few hours? A pure sine wave UPS is enough, and it switches over automatically without you needing to be at home. Handy detail: it also protects your boiler electronics from voltage spikes.
Do you want to be self-sufficient for a day or two? A 1 to 2 kWh power station with LiFePO4 cells and a UPS function gives most people the best value for money. It is portable too, so you can use it for other things.
Do you want to stop thinking about it altogether? A permanent installation with an inverter, battery and automatic changeover switch, fitted by an installer. Your whole backup circuit then switches over without you lifting a finger.
Do you have solar panels? Then take note: an ordinary solar installation shuts itself down automatically when the grid goes down. That is a mandatory safety function so that no voltage is put onto a network that engineers are working on. Solar panels on their own therefore give you no backup power. For that you need an inverter with a backup function or a separate battery.
The simple route: sorted in 20 minutes
For the vast majority of houses this is enough. First have a look at how your boiler is connected.
Is there a plug in a socket next to the boiler? Then you are nearly there:
- Buy a power station or UPS with a pure sine wave output and at least 500 W continuous (800 W or more is comfortable for the start-up peak).
- Put it within reach of the boiler, somewhere dry, not in a sealed cupboard.
- Test it fully once: plug out, into the backup supply, thermostat up, boiler must ignite and stay lit.
- Test your thermostat as well. If it runs on batteries, you are fine. If it hangs off the mains or off a wifi gateway with its own adapter, that needs to be on your backup supply too.
- Top it up every three to six months and put that in your diary.
Is your boiler hard-wired, with no plug? Then there are two routes: have an installer fit a socket so you can swap the supply over, or go straight for a permanent backup supply with a changeover switch. Do not start fiddling with a hard-wired appliance yourself.
Do not forget the rest of the chain
This is the second place where it goes wrong: people neatly arrange power for the boiler and still end up sitting in the cold.
The room thermostat. With no call for heat, your boiler does nothing. Check whether your thermostat runs on batteries (in which case there is nothing to worry about) or on the mains or a separate adapter (in which case it needs to go on your backup supply). Some smart thermostats have a permanent 230 V supply or a gateway in the meter cupboard.
The internet connection. A smart thermostat that pulls its settings from the cloud may fall back to a fixed setpoint during an outage. Find out what your model does when the internet disappears, and how to set it to a temperature by hand. Look that up before it is dark and cold.
The underfloor heating pump. If you have underfloor heating with a separate pump group on the manifold, that often sits on its own supply and not on the boiler. Without that pump your floor gets no water.
Zone valves and a second pump. Larger systems sometimes have several circuits. Have a quick look at all the little devices hanging off it.
The carbon monoxide alarm. It should run on batteries, but check. In an emergency involving heaters and generators is exactly when you want it working.
Practical approach: write a note for the meter cupboard listing which plugs need to go into the backup supply during an outage. Standing in the dark with a torch is not the moment you want to start working it out.
Generators: when they make sense, and how to use them safely
A generator is the logical choice if you want to ride out days rather than hours, or power more than just the heating. But there are hard safety rules attached.
1. Never indoors, never in the garage, never in a shed attached to the house. A combustion engine produces carbon monoxide, an odourless gas that kills people while they sleep. An open garage door is not enough either. Put it outside, away from windows, doors and vents, and make sure you have working carbon monoxide alarms in the house.
2. Never backwards into a socket. Connecting a generator to your house wiring via an extension lead with a plug on both ends is lethally dangerous. You put the exposed pins of that lead live, and you can feed voltage back into the network that engineers are working on.
3. If you want the generator on your house wiring, that requires a changeover switch fitted by a registered installer. Dutch grid operator guidance states that back-feeding into the distribution network must be technically impossible on a permanent generator connection. Source: Noodstroomvoorziening Friesland (in Dutch) The rule is the same wherever you live, for the same reason. A good changeover switch disconnects the grid first, before the generator can be connected.
4. Choose an inverter generator. Those deliver a clean sine wave and a stable frequency, even when the load varies. A cheap site generator with a simple alternator head puts out a voltage that wanders with the load, and your boiler electronics will not enjoy that one bit.
5. Assume the neutral is floating. See trap 3. Have an installer assess how the neutral and earth need to be arranged for your particular combination.
6. Think about the fuel. Petrol in jerrycans ages. For longer storage there is fuel stabiliser, and always store it outside the house in a well ventilated space. A generator running on LPG or bottled gas does not have that problem, but it comes with storage rules of its own.
What if you have a heat pump?
Completely different story, and worth knowing before you buy a power station.
A heat pump uses 800 to 2,500 watts while running, with a start-up demand of 3,000 to 6,000 watts. Source: Noodstroom Thuis (in Dutch) That start-up figure is the killer: plenty of home batteries and power stations have a 3,600 W inverter, and that simply will not cope with a start like that.
What does that mean in practice?
- A heat pump on backup power is a serious project. Reckon on an inverter with a lot of peak capacity and a substantial battery, because 1,500 W averaged over 24 hours is already 36 kWh.
- Check whether your unit has a soft start or an inverter-driven compressor. Modern inverter heat pumps start far more gently than an on-off model.
- Consider a different strategy. For most people it is more realistic to keep one room warm with an alternative heat source during a longer outage than to keep the entire heat pump running.
For a gas boiler, backup power is a matter of a couple of hundred euros. For a heat pump you are talking about a completely different order of magnitude.
What does it cost? Three realistic packages
| Package | What is in it | Cost | What you get |
|---|---|---|---|
| Basic | Pure sine wave UPS, 500 to 800 W | 150 to 400 euros | a few hours covered, automatically |
| Comfort | 1 to 2 kWh LiFePO4 power station with UPS function, plus an extension lead | 600 to 1,500 euros | 24 hours or more of heating, plus fridge and lights |
| Complete | Inverter and battery permanently installed, changeover switch, installation work | 2,000 to 5,000 euros | several days, automatic, whole backup circuit |
For the permanent installation, reckon on 500 to 1,500 euros of installation costs for a changeover switch and a separate backup circuit, depending on your consumer unit and the distance involved.
Maintenance: the step everybody skips
A backup supply you never test is not a backup supply. That sounds harsh, but it is exactly what happens: people buy something, put it in the utility room and discover four years later that the battery is flat and dead.
| What | How often |
|---|---|
| Top up power station or UPS | every 3 to 6 months |
| Real test with the boiler (ignite and stay lit) | once a year, in autumn |
| Check lead-acid batteries on a permanent installation | once a year |
| Run the generator up | every six months, at least 15 minutes under load |
| Refresh the fuel | annually, or use stabiliser |
Do not store a lithium power station permanently at 100 per cent, and not empty either. Somewhere between 50 and 80 per cent is kindest to its lifespan, but make sure it is full going into the heating season.
Put that annual test in your diary for October, along with testing your smoke alarms and your carbon monoxide alarm. One evening, all done in one go.
The 8 most common mistakes
- Buying an inverter without a pure sine wave output. The boiler goes into lockout or the electronics take damage.
- Never testing it. You then find the problem only when it really matters.
- Forgetting the thermostat. Boiler has power, but gets no call for heat.
- Ignoring the floating neutral. Flame failure on a generator, and nobody understands why.
- Putting a generator indoors or in the garage. Lethally dangerous because of carbon monoxide.
- Hooking a generator to the wiring with a double-ended lead. Lethally dangerous for you and for network engineers.
- Sizing it too small. Size for the start-up peak, not for the average.
- Thinking solar panels give you backup power. They shut down when the grid fails, which is the opposite.
Frequently asked questions
Does my gas boiler work during a power cut?
No. Without electricity the fan, the ignition, the gas valve and the circulation pump do not work, so your boiler will not start. The gas is usually still there, because the gas network does not run on your electricity. You only need a couple of hundred watts of backup power to get everything working again.
How many watts do I need to run a gas boiler on backup power?
Reckon on 80 to 200 watts while running and a start-up peak of 200 to 400 watts. Choose a backup supply with at least 500 watts continuous so there is headroom for the start-up peak and for your thermostat. If you want a fridge, some lights and your router on it too, you are quickly looking at 800 to 1,000 watts of peak capacity.
How long can a power station keep my gas boiler running?
On an average winter’s day, with a boiler running about 40 per cent of the time, heating costs you roughly 1.5 kWh per 24 hours. A 1 kWh power station will therefore get you about half a day, and 2 kWh a little over a full day. Turn the thermostat down and heat one room only, and you will easily get double that.
Can I connect my gas boiler to a generator?
You can, but there are two conditions. First, the generator has to deliver a stabilised voltage at a clean 50 Hz, so choose an inverter generator and not a crude site generator. Second, the ionisation current of the flame supervision runs to earth, and many generators have a floating neutral with no earth reference. Your boiler will then go into flame failure. Have a registered installer assess how the neutral and earth should be arranged for your particular combination, and do not bodge it yourself.
Why does my boiler go into lockout on backup power even though there is voltage?
The three most common causes: no pure sine wave (the electronics will not accept the waveform), live and neutral swapped (many boilers are polarity sensitive), or no earth reference for the ionisation current of the flame supervision. That last one gives the classic picture of a boiler that starts and then drops straight back into flame failure.
Can I connect a generator to my consumer unit myself?
Do not do it yourself. On a permanent generator connection, back-feeding into the distribution network has to be technically impossible, and that is arranged with a certified changeover switch fitted by a registered installer. Connecting it wrongly can put network engineers’ lives at risk, and if something goes wrong it can cause problems with your insurance.
Will my solar panels give me power during an outage?
No, not without extra kit. An ordinary solar installation is required to shut down when the grid fails, so that no voltage is put onto the network. If you want to benefit from your panels during an outage, you need an inverter with a backup function or a home battery with a backup supply, feeding a separate circuit that is isolated from the grid.
Is a UPS from the computer shop good enough?
Only if it is a pure sine wave model, and those cost more than the entry-level ones. The cheap computer UPS units deliver an approximated sine wave, and boiler electronics can trip up on that. Watch the runtime too: a computer UPS is designed to shut a PC down tidily and often delivers only 5 to 20 minutes of power.
The short version: your gas boiler asks for very little, so backup power is both achievable and affordable. Buy something with a pure sine wave output, size it for the start-up peak, do not forget your thermostat, and test it once on an ordinary Tuesday evening in October. Then you know for certain that come January you will not be standing in a cold house looking at a boiler that has gas but no electricity.
Mainly want to be less dependent on your heating in the first place? In the Energie Verpulveraar I go through step by step how to tackle your house so that you are comfortable on less heat: insulation, draught proofing and the measures that genuinely deliver. Have a look.
Regards from Fred Schouten, builder and DIYer through and through
PS: put a note in your meter cupboard saying which plugs go where during an outage. With a torch in your mouth on a cold evening, that is the last thing you want to be working out. Small tip. Big difference.